Leak detector LAG-14 ER

Code: AF.DE.0013

For monitoring inflammable liquids of danger classes A I, A
II, A III, B (according to former classification VbF) and noninflammable
water-polluting liquids stored aboveground. The LAG container can be installed in hazardous
areas zones I and II (e.g. manhole pit of petrol tanks). Approved for tanks according to EN 12285-1,
12285-2, DIN 6618-1, 6619-1, 6623-1 and DIN 6624-1 under atmospheric conditions.
Since July 2003, the LAG-14 leak detector may only be used for replacement deliveries for underground,
double-walled tanks as a result of the reclassification of water-polluting liquids in Germany!


Class II leak detector (EN 13160-1), with intrinsically safe probe circuit. The system consists of a control
unit, a container for leak detection fluid (LAG container black) and a probe. Control unit with operating and
alarm indicators, audible/visual alarm, test button and increased interference protection. The audible
alarm can be muted with the Acknowledge button. The voltage-free relay contact is provided for connection
of additional external alarm equipment (such as horns, EMS event reporting system). Suitable
for panel mounting with a mounting frame; a sealing kit (IP 54) is available for rough application conditions.
The LAG container serves as detection container and as expansion vessel at the same time. For
aboveground tanks, the ratio between usable contents and total volume of leak detection fluid must be
no more than 1:35. An additional container must be used if the ratio exceeds this value.