[minicart_error]
For monitoring inflammable liquids of danger classes A I, AII, A III, B (according to former classification VbF) and noninflammablewater-polluting liquids stored aboveground. The LAG container can be installed in hazardousareas zones I and II (e.g. manhole pit of petrol tanks). Approved for tanks according to EN 12285-1,12285-2, DIN 6618-1, 6619-1, 6623-1 and DIN 6624-1 under atmospheric conditions.Since July 2003, the LAG-14 leak detector may only be used for replacement deliveries for underground,double-walled tanks as a result of the reclassification of water-polluting liquids in Germany!
Class II leak detector (EN 13160-1), with intrinsically safe probe circuit. The system consists of a controlunit, a container for leak detection fluid (LAG container black) and a probe. Control unit with operating andalarm indicators, audible/visual alarm, test button and increased interference protection. The audiblealarm can be muted with the Acknowledge button. The voltage-free relay contact is provided for connectionof additional external alarm equipment (such as horns, EMS event reporting system). Suitablefor panel mounting with a mounting frame; a sealing kit (IP 54) is available for rough application conditions.The LAG container serves as detection container and as expansion vessel at the same time. Foraboveground tanks, the ratio between usable contents and total volume of leak detection fluid must beno more than 1:35. An additional container must be used if the ratio exceeds this value.